MR-F-LD6 Modbus RTU

910033
909848
909853
909856
909859
910158
909338
Description

The Modbus module with 6 analog inputs and 2 relay outputs was developed for decentralized switching tasks. Suitable to monitor electrodes of leakage sensors or the fill level of fluid containers and to switch pumps or magnetic valves. In this case it is necessary to protect the relay contacts by appropriate load-dependent measures. The resistance of the conductive fluid is measured when the electrodes are immersed. It is also possible to signal a cable break (requires sensor LKS-ZD). The module can be operated independently or via a Modbus master. Inputs and outputs can be switched and scanned via standard registers. Module address, bit rate and parity are set with two rotary switches on the front or by software. Suitable for decentralized mounting on DIN TH35 rail according to IEC 60715 in electrical distribution cabinets.

  • Connection with spring clamp terminal blocks (push-in)
logo_culs_listed
Technical Data
General Data
Modbus RTU
00 to F9
RS485 (two-wire bus)
1200 to 115200 bit/s
24 V AC/DC +/- 10 % (SELV)
80 mA (AC) / 43 mA (DC)
100 %
connection of the electrodes
common reference potential
20 kOhm
3 Veff, 70 Hz at resistance measurement
+/-10 % with sensor resistance 4 to 40 kOhm; +/-20 % with sensor resistance 2 to 100 kOhm
+/-16 V at wire break monitoring
6.2 to 10 V can be used as line termination
40 nF max. equates 400 m at 100 nF/km
1.5 s
2 NO contacts (SPST-NO)
250 V AC
6 A / output
Green, red and yellow LED
50 x 69.3 x 60 mm
126 g
-5 °C to 55 °C
-20 °C to 70 °C
IP40 / IP20
Check US distributor inventory
Accessories
Accessory of
Part number
1108441370
4251394620725
Downloads
FAQ's

What can I do if the red ERROR LED on the module lights up or there is no communication?

There are several possible causes, please check the following:

- Operating voltage (A1 / A2) connected and sufficient for the device.
- BUS (A- / B+) connected and not reversed. Pay attention to (- / +), not to A/B.
- Address (rotary switches) set correctly, must not occur twice or be 0.
- Bit rate and parity (rotary switches) set correctly, only possible in programming mode (see mounting note).
- Shielded and twisted pair cable used.
- Termination resistor (120 Ω) set on both sides.
- Bias resistors available on the BUS.
- Timeout high enough for all participants to respond (approx. 10 ms).

What can I do if the red ERROR LED on the module lights up or there is no communication?

There are several possible causes, please check the following:

- Operating voltage (A1 / A2) connected and sufficient for the device.
- BUS (A- / B+) connected and not reversed. Pay attention to (- / +), not to A/B.
- Address (rotary switches) set correctly, must not occur twice or be 0.
- Bit rate (rotary switches) set correctly, only possible in programming mode (see mounting note).
- Shielded and twisted pair cable used.
- Termination resistor (120 Ω) set on both sides.
- Bias resistors available on the BUS.
- Max Master as high as the number of physical master I/Os on the BUS.
- Max Frame high enough for all answers from participants to get through (BMT-RTR setting).